Series Vents VPVO

Axial fans with air flow up to 120 000 m³/h
  • Impeller type: Axial
  • Casing material: Coated steel
PURPOSE

In general ventilation systems in industrial, administrative and residential buildings. As a part of a smoke extraction system for air pressurization to create a positive air pressure differential in stairway enclosures, airlock vestibules and lift shafts, to prevent spreading of smoke in premises, protect people using evacuation routes from fire hazards and enable conditions for fire-extinguishing measures.


DESIGN

The metal casing with rolled flanges helps achieve outstanding rigidity and minimum clearances between the casing and the blades. There is an inspection hatch in the casing for easy maintenance. All the casing components are powder coated for improved protection against the environmental effects. The weight of the fans may differ from the one stated in the catalogue and depends on the components used (motor, terminal box, etc.).


MOTOR

The fans are equipped with three-phase (400 V/50 Hz) single-speed 2-, 4- or 6-pole electric motors. Motor ingress protection level – IP55.

IMPELLER

Depending on the size and the required air capacity the fans are equipped with impellers with 6 or 8 blades angled from 20° to 50° with variation from 2.5 up to 5° to ensure precise matching of fans with the operating point. The fan uses specially designed impeller blades. The impellers are dynamically balanced. Low weight and low moment of the impeller inertia help reduce the fan start-up time. The fan blades can be made of the following materials: PAG – fiberglass reinforced polyamide AL – aluminium. Please confirm the blade material while placing your order.


INSTALLATION

The fans can be mounted on any flat surface or directly into a ventilation duct. The units are suitable for both horizontal and vertical configurations. In-duct installation requires flanges to attach the fan to the ductwork. To attach the fan to the floor, a wall or the ceiling use the O-VO carriers (not included as standard, should be purchased separately). The units are suitable for installation on rooftops to provide direct supply of outdoor air to the stairway areas.

COMPLETE SOLUTIONS FOR AXIAL FANS


INSTALLATION EXAMPLE OF AXIAL FANS ON ROOFTOP


Filters: Connected air duct size: 500 mm
Lineup Vents VPVO Connected air duct size, mm Rated power, W Maximum airflow, m³/h Number of blades, pcs. Blade setting angle, degrees Impeller material
500 1100 9300 6 25 Aluminium
500 1500 11600 6 30 Aluminium
500 2200 14200 6 35 Aluminium
500 3000 15200 8 35 Aluminium
500 4000 17200 8 40 Aluminium
500 5500 19600 8 45 Aluminium
500 1100 9300 6 25 Fiberglass reinforced polyamide
500 1500 11600 6 30 Fiberglass reinforced polyamide
500 2200 14200 6 35 Fiberglass reinforced polyamide
500 3000 15200 8 35 Fiberglass reinforced polyamide
500 4000 17200 8 40 Fiberglass reinforced polyamide
500 5500 19600 8 45 Fiberglass reinforced polyamide
500 180 4600 6 25 Aluminium
500 250 5800 6 30 Aluminium
500 370 7100 6 35 Aluminium
500 370 7900 6 40 Aluminium
500 550 9200 6 45 Aluminium
500 750 9800 8 45 Aluminium
500 180 4600 6 25 Fiberglass reinforced polyamide
500 250 5800 6 30 Fiberglass reinforced polyamide
500 370 7100 6 35 Fiberglass reinforced polyamide
500 370 7900 6 40 Fiberglass reinforced polyamide
500 550 9200 6 45 Fiberglass reinforced polyamide
500 750 9800 8 45 Fiberglass reinforced polyamide