Series Vents VPVO

Axial fans with air flow up to 120 000 m³/h
  • Impeller type: Axial
  • Casing material: Coated steel
PURPOSE

In general ventilation systems in industrial, administrative and residential buildings. As a part of a smoke extraction system for air pressurization to create a positive air pressure differential in stairway enclosures, airlock vestibules and lift shafts, to prevent spreading of smoke in premises, protect people using evacuation routes from fire hazards and enable conditions for fire-extinguishing measures.


DESIGN

The metal casing with rolled flanges helps achieve outstanding rigidity and minimum clearances between the casing and the blades. There is an inspection hatch in the casing for easy maintenance. All the casing components are powder coated for improved protection against the environmental effects. The weight of the fans may differ from the one stated in the catalogue and depends on the components used (motor, terminal box, etc.).


MOTOR

The fans are equipped with three-phase (400 V/50 Hz) single-speed 2-, 4- or 6-pole electric motors. Motor ingress protection level – IP55.

IMPELLER

Depending on the size and the required air capacity the fans are equipped with impellers with 6 or 8 blades angled from 20° to 50° with variation from 2.5 up to 5° to ensure precise matching of fans with the operating point. The fan uses specially designed impeller blades. The impellers are dynamically balanced. Low weight and low moment of the impeller inertia help reduce the fan start-up time. The fan blades can be made of the following materials: PAG – fiberglass reinforced polyamide AL – aluminium. Please confirm the blade material while placing your order.


INSTALLATION

The fans can be mounted on any flat surface or directly into a ventilation duct. The units are suitable for both horizontal and vertical configurations. In-duct installation requires flanges to attach the fan to the ductwork. To attach the fan to the floor, a wall or the ceiling use the O-VO carriers (not included as standard, should be purchased separately). The units are suitable for installation on rooftops to provide direct supply of outdoor air to the stairway areas.

COMPLETE SOLUTIONS FOR AXIAL FANS


INSTALLATION EXAMPLE OF AXIAL FANS ON ROOFTOP


Filters: Connected air duct size: 450 mm
Lineup Vents VPVO Connected air duct size, mm Rated power, W Maximum airflow, m³/h Number of blades, pcs. Blade setting angle, degrees Impeller material
450 750 7500 6 25 Aluminium
450 1100 9000 6 30 Aluminium
450 1500 11100 6 35 Aluminium
450 2200 12400 6 40 Aluminium
450 3000 13000 8 40 Aluminium
450 4000 15000 8 45 Aluminium
450 750 7500 6 25 Fiberglass reinforced polyamide
450 1100 9000 6 30 Fiberglass reinforced polyamide
450 1500 11100 6 35 Fiberglass reinforced polyamide
450 2200 12400 6 40 Fiberglass reinforced polyamide
450 3000 13000 8 40 Fiberglass reinforced polyamide
450 4000 15000 8 45 Fiberglass reinforced polyamide
450 120 3700 6 25 Aluminium
450 180 4500 6 30 Aluminium
450 250 5600 6 35 Aluminium
450 250 6200 6 40 Aluminium
450 370 7100 6 45 Aluminium
450 550 7500 8 45 Aluminium
450 120 3700 6 25 Fiberglass reinforced polyamide
450 180 4500 6 30 Fiberglass reinforced polyamide
450 250 5600 6 35 Fiberglass reinforced polyamide
450 250 6200 6 40 Fiberglass reinforced polyamide
450 370 7100 6 45 Fiberglass reinforced polyamide
450 550 7500 8 45 Fiberglass reinforced polyamide
Datasheet
"VENTS VPVO (smoke extraction)" product description 10-2025
1.9 Mb
Datasheet
"VENTS VPVO (сommercial and industrial ventilation)" product description 09-2025
1.97 Mb
Manual
"VENTS VPVO" user's manual 08-2023 (V118EN-05)
2.71 Mb
BIM/CAD models
VPVO
4.05 Mb
Image
VPVO - image 1
500 Kb