Vents VKMz 250

Centrifugal inline fans in galvanized casing
  • Sound pressure level LpA at 3 m: 52 dB(A)
  • Impeller type: Centrifugal impeller with backward curved blades
  • Casing material: Galvanized steel
  • Installation in any position
Unit of measurement VKMz 250
Connected air duct size mm 250
Phases - 1
Minimum supply voltage V 220
Maximum supply voltage V 240
Power supply frequency Hz 50 60
Rated power W 152
Unit current A 0.66
Maximum airflow m³/h 1070
Rotation speed at 50hz - 2765
Sound pressure level LpA at 3 m dB(A) 52
Weight kg 5.1
Transported air temperature (max) °С 50
Transported air temperature (min) °С -25
Ingress protection rating - IPX4
Ingress protection rating of the drive - IP44
Impeller material - Plastic
Vents VKMz 250 52 980 2016
Trademark Vents
Model VKMz 250
Specific energy consumption (SEC) (kWh/(m²/a)) Cold Average Warm
-53.7 A+ -26.7 B -11.2 E
Type of ventilation unit Unidirectional
Type of drive installed Variable speed
Type of heat recovery system None
Maximum flow rate (m³/h) 980
Electric power input (W) 152
Reference flow rate (m³/s) 0.191
Reference pressure difference (Pa) 50
Specific power input (SPI) (W/(m³/h)) 0.122
Control typology Local demand control
Maximum external leakage rates (%) 2.7
Sound power level (dB(A)) 52
Declared typology RVU UVU
The annual electricity consumption (AEC) (kWh/a) Cold Average Warm
64 64 64
The annual heating saved (AHS) (kWh/a) Cold Average Warm
5536 2830 1280
Datasheet
"VENTS VKMz" product description 03-2026
2.26 Mb
Manual
"VENTS VKMz" user's manual 04-2026 (V05-1EN-12)
995 Kb
BIM/CAD models
VKMz
2.5 Mb
Image
VKMz 250 - image 1
620 Kb
Image
VKMz 250 - image 2
640 Kb
Image
VKMz 250 - image 3
636 Kb
Image
VKMz 250 - image 4
554 Kb
ØD ØD1 B B1 L L1 L2 L3
249 332 340 380 213 25 29 40