Vents VKMK 250

Roof centrifugal fans
  • Sound pressure level LpA at 3 m: 52 dB(A)
  • Impeller type: Centrifugal impeller with backward curved blades
  • Casing material: Coated steel
Unit of measurement VKMK 250
Connected air duct size mm 250
Phases - 1
Minimum supply voltage V 220
Maximum supply voltage V 240
Power supply frequency Hz 50/60
Rated power W 194
Unit current A 0.85
Maximum airflow m³/h 1310
Rotation speed at 50hz - 2790
Sound pressure level LpA at 3 m dB(A) 52
Weight kg 10.1
Transported air temperature (max) °С 50
Transported air temperature (min) °С -25
Ingress protection rating - IPX4
Ingress protection rating of the drive - IP44
Impeller material - Plastic
Size mm 250
Trademark Vents
Model VKMK 250
Type of drive installed External MSD or VSD
Type of heat recovery system None
Nominal external pressure (Pa) 331
Maximum external leakage rates (%) 2.7
Static efficiency (%) 32.2
Declared typology NRVU UVU
Effective electric power input (kW) 0.182
Sound power level (dB(A)) 72
Datasheet
"VENTS VKMK" product description 10-2025
944 Kb
Manual
"VENTS VKMK, VKMKp" user's manual 07-2026 (V292EN-01)
730 Kb
Manual
"VENTS VKV, VKH, VKV EC, VKH EC, VKMK, VKMKp, VOK, VOK1" user's manual 01-2021 (V12EN-09)
2.05 Mb
Image
VKMK 250 - image 1
324 Kb
∅D ∅D1 H L L1
248 400 249 590 450
Name Photo Description
Vents RSA5E-3,5-T RSA5E-3,5-T Speed controllers are applied for air flow control of single phase fans by means of motor step speed control
Vents RSA5E-5,0-T RSA5E-5,0-T Speed controllers are applied for air flow control of single phase fans by means of motor step speed control
Vents RSA5E-7,5-T RSA5E-7,5-T Speed controllers are applied for air flow control of single phase fans by means of motor step speed control
Name Photo Description
Vents RKV 250-315 RKV 250-315 Mounting frame
Vents RKVI 250-315 RKVI 250-315 Mounting frame with thermal-insulating layer