Vents VUT 300 PBE EC L A21

Suspended air handling units with a counterflow polystyrene or enthalpy heat exchanger
  • Power of electrical reheater: 1500 W
  • Sound pressure level LpA at 3 m: 27 dB(A)
  • Heat exchanger type: Counter flow
  • Heat exchanger material: Polystyrene
  • Sound-insulated casing
  • Bypass: Auto
  • Reheater: Electric
  • Preheater: Optional
  • BMS protocol: ModBus
  • Control: Smartphone
  • Casing material: Galvanized steel
  • Humidity sensor: Optional
  • CO2 sensor: Optional
  • PM2.5 sensor: Optional
Unit of measurement VUT 300 PBE EC L A21
Phases - 1
Minimum supply voltage V 230
Maximum supply voltage V 230
Power supply frequency Hz 50/60
Rated power W 180
Power of electrical reheater W 1500
Unit current A 7.9
Maximum airflow m³/h 340
Sound pressure level LpA at 3 m dB(A) 27
Heat recovery efficiency, max % 90
Heat exchanger type - Counter flow
Heat exchanger material - Polystyrene
Weight kg 44
Transported air temperature (max) °С 40
Transported air temperature (min) °С -25
Ambient air temperature min °С 1
Ambient air temperature max °С 40
Ingress protection rating - IP22
Ingress protection rating of the drive - IP44
Ambient air humidity max % 60
Vents VUT 300 PBE EC L A21 49 295 2016
Trademark Vents
Model VUT 300 PBE EC L A21
Specific energy consumption (SEC) (kWh/(m²/a)) Cold Average Warm
-75.7 A+ -39 A -15.3 E
Type of ventilation unit Bidirectional
Type of drive installed Variable speed
Type of heat recovery system Recuperative
Thermal efficiency of heat recovery (%) 76
Maximum flow rate (m³/h) 295
Electric power input (W) 174
Reference flow rate (m³/s) 0.061
Reference pressure difference (Pa) 50
Specific power input (SPI) (W/(m³/h)) 0.35
Control typology Local demand control
Maximum internal leakage rates (%) 2.7
Maximum external leakage rates (%) 2.7
Sound power level (dB(A)) 49
Declared typology RVU BVU
The annual electricity consumption (AEC) (kWh/a) Cold Average Warm
767 230 185
The annual heating saved (AHS) (kWh/a) Cold Average Warm
8614 4403 1991
Datasheet
"VENTS VUT/VUE PBE/PBW EC" product description 03-2025
2.85 Mb
Manual
"VENTS VUT/VUE PBE EC" user’s manual 01-2026 (V217-3EN-02)
3.11 Mb
Manual
"VENTS VUT 2000-3000 PBE EC" user’s manual 02-2025 (V225-1EN-04)
4.37 Mb
Manual
"Wireless control system A21" user’s manual 02-2023 (V55-8EN-05)
504 Kb
BIM/CAD models
VUT/VUE PBE/PBW EC - BIM model
2.35 Mb
BIM/CAD models
VUT(E) 300 PBE EC L - BIM model
562 Kb
Image
VUT 300 PBE EC L A21 - image 1
347 Kb
∅D B B1 H L L1
160 485 577 280 1238 1291