Vents VKM 160

Centrifugal inline fans
  • Sound pressure level LpA at 3 m: 45 dB(A)
  • Impeller type: Centrifugal impeller with backward curved blades
  • Casing material: Coated steel
  • Installation in any position
Unit of measurement VKM 160
Connected air duct size mm 160
Phases - 1
Minimum supply voltage V 220
Maximum supply voltage V 240
Power supply frequency Hz 50/60
Rated power W 99
Unit current A 0.44
Maximum airflow m³/h 567
Rotation speed at 50hz - 2770
Sound pressure level LpA at 3 m dB(A) 45
Weight kg 5
Transported air temperature (max) °С 45
Transported air temperature (min) °С -25
Ingress protection rating - IPX4
Ingress protection rating of the drive - IP44
Impeller material - Plastic
Vents VKM 160 67 429 2016
Trademark Vents
Model VKM 160
Specific energy consumption (SEC) (kWh/(m²/a)) Cold Average Warm
-51.3 A+ -24.2 C -8.7 F
Type of ventilation unit Unidirectional
Type of drive installed Variable speed
Type of heat recovery system None
Maximum flow rate (m³/h) 429
Electric power input (W) 99
Reference flow rate (m³/s) 0.083
Reference pressure difference (Pa) 50
Specific power input (SPI) (W/(m³/h)) 0.31
Control typology Local demand control
Maximum external leakage rates (%) 2.7
Declared typology RVU UVU
Sound power level (dB(A)) 67
The annual electricity consumption (AEC) (kWh/a) Cold Average Warm
164 164 164
The annual heating saved (AHS) (kWh/a) Cold Average Warm
5536 2830 1280
Datasheet
"VENTS VKM" product description 08-2023
1.68 Mb
Manual
"VENTS VKM" user's manual 04-2026 (V05EN-12)
1.09 Mb
Manual
"VENTS VKM(S)" user's manual 04-2026 (V05-3EN-02)
915 Kb
BIM/CAD models
VKM
4.24 Mb
Image
VKM 160 - image 1
467 Kb
ØD ØD1 B B1 L L1 L2 L3
159 305 360 320 220 25 25 30