Vents VKM 100 EC E

Centrifugal inline fans with EC-motors
  • Sound pressure level LpA at 3 m: 44 dB(A)
  • Impeller type: Centrifugal impeller with backward curved blades
  • Casing material: Coated steel
  • Installation in any position
Unit of measurement VKM 100 EC E
Connected air duct size mm 100
Phases - 1
Minimum supply voltage V 230
Maximum supply voltage V 230
Power supply frequency Hz 50/60
Rated power W 72
Unit current A 0.58
Maximum airflow m³/h 318
Rotation speed at 50hz - 3500
Sound pressure level LpA at 3 m dB(A) 44
Transported air temperature (max) °С 45
Transported air temperature (min) °С -25
Ingress protection rating - IPX4
Impeller material - Plastic
Vents VKM 100 EC E 64 280 2016
Trademark Vents
Model VKM 100 EC E
Specific energy consumption (SEC) (kWh/(m²/a)) Cold Average Warm
-53.3 A+ -26.3 B -10.8 E
Type of ventilation unit Unidirectional
Type of drive installed Variable speed
Type of heat recovery system None
Maximum flow rate (m³/h) 280
Electric power input (W) 70
Reference flow rate (m³/s) 0.054
Reference pressure difference (Pa) 50
Specific power input (SPI) (W/(m³/h)) 0.153
Control typology Local demand control
Maximum external leakage rates (%) 2.7
Declared typology RVU UVU
Sound power level (dB(A)) 64
The annual electricity consumption (AEC) (kWh/a) Cold Average Warm
81 81 81
The annual heating saved (AHS) (kWh/a) Cold Average Warm
5536 2830 1280
Datasheet
"VENTS VKM EC" product description 08-2023
2.7 Mb
Manual
"VENTS VKM EC" user's manual 03-2026 (V88EN-09)
2.39 Mb
Manual
"VENTS VKM 100-200 EC" user's manual 02-2026 (V88-3EN-01)
2.93 Mb
BIM/CAD models
VKM EC
4.19 Mb
Image
VKM 100 EC E - image 1
653 Kb
ØD ØD1 B B1 H L L1 L2 L3
99 245 300 260 330 195 20 20 30